# Building Manager's Annual Compliance Calendar

**Standfirst:** The recurring statutory and best-practice testing regime for a UK commercial, residential or mixed-use building, with frequencies and the standards behind them.

## Section 01 · Fire safety

| Task | Frequency | Reference |
|---|---|---|
| Fire alarm user test (call point rotation) | Weekly | BS 5839-1 |
| Fire alarm service by competent person | At least 6-monthly (all devices over 12 months) | BS 5839-1 |
| Emergency lighting function test | Monthly | BS 5266-1 / BS EN 50172 |
| Emergency lighting full duration (3-hour) test | Annual | BS 5266-1 |
| Fire door checks — common parts (residential over 11m) | Quarterly | Fire Safety (England) Regs 2022, reg 10 |
| Flat entrance door checks (residential over 11m) | Annual (best endeavours) | Fire Safety (England) Regs 2022, reg 10 |
| Firefighting lift and equipment checks (high-rise residential) | Monthly | Fire Safety (England) Regs 2022 |
| Fire extinguisher visual check | Monthly | BS 5306-3 |
| Fire extinguisher service | Annual (extended 5-yearly; CO₂ 10-yearly) | BS 5306-3 |
| Dry riser visual inspection | 6-monthly | BS 9990 |
| Dry riser wet pressure test | Annual | BS 9990 |
| Sprinkler system checks | Weekly checks; quarterly flow and pump; annual service | BS EN 12845 / BS 9251 / LPC Rules |
| Fire risk assessment review | Regularly and on significant change [common practice: annual] | FSO 2005, art. 9 |
| Evacuation drill | [Annual, or per FRA] | FSO 2005 / FRA |

## Section 02 · Water hygiene

| Task | Frequency | Reference |
|---|---|---|
| Sentinel outlet temperature monitoring (hot ≥50°C at outlet, stored ≥60°C; cold under 20°C) | Monthly | ACOP L8 / HSG274 |
| Infrequently used outlet flushing | Weekly | HSG274 Part 2 |
| Shower head clean and descale | Quarterly | HSG274 Part 2 |
| Cold water storage tank inspection | Annual | HSG274 Part 2 |
| Legionella risk assessment review | Typically every 2 years and on change | ACOP L8 |
| Records retained | 5 years | ACOP L8 |

*Includes a Monthly Monitoring Log: Month / Temperatures / Flushing / By.*

> Water hygiene records must be retained for five years — build the storage route before the first month's readings, not after.

## Section 03 · Lifts, electrical, gas and plant

| Task | Frequency | Reference |
|---|---|---|
| Passenger lift thorough examination | 6-monthly | LOLER 1998, reg 9 |
| Goods-only lift thorough examination | 12-monthly | LOLER 1998, reg 9 |
| Lift maintenance visits | Per contract [commonly monthly or quarterly] | Manufacturer / SAFed |
| Trapped passenger release competence confirmed for the building team | Ongoing / on staff change | BS 7255 |
| Fixed wiring inspection (EICR) — commercial | 5-yearly maximum | BS 7671 / EAWR 1989 |
| Fixed wiring inspection (EICR) — industrial | 3-yearly | BS 7671 |
| Portable appliance testing | Risk-based | HSE guidance |
| Gas safety check (commercial CP17 / catering CP42) | Annual | Gas Safety (Installation and Use) Regs 1998 |
| Lightning protection test | Annual (11-month rolling best practice) | BS EN 62305 |
| Fall arrest and anchor point examination | 12-monthly | Work at Height Regs 2005 / LOLER |
| Air conditioning inspection (systems over 12kW) | 5-yearly | EPB Regs 2012 / CIBSE TM44 |
| Pressure systems written scheme examination | Per written scheme | PSSR 2000 |

## Section 04 · Asbestos, access and general

| Task | Frequency | Reference |
|---|---|---|
| Asbestos management plan review | At least 12-monthly | CAR 2012, reg 4 |
| Asbestos re-inspection survey | Risk-based, 6 to 12 monthly | HSG264 |
| Automatic door safety inspection | [6-monthly recommended] | BS EN 16005 |
| Roller shutter and powered gate service | [6-monthly recommended] | Machinery regs / manufacturer |
| CCTV system check including retention verification | [Monthly recommended] | UK GDPR / ICO guidance |
| Access control audit (leavers removed, fobs reconciled) | [Quarterly recommended] | Good practice |
| First aid kit and AED checks | [Monthly recommended] | Health and Safety (First-Aid) Regs 1981 |
| Accessibility review (Equality Act reasonable adjustments) | [Annual recommended] | Equality Act 2010 |

**How to read this calendar:** Frequencies in brackets are recommended good practice rather than fixed statutory intervals. The statutory hook for most testing is the duty to maintain — under the Fire Safety Order, the Electricity at Work Regulations or health and safety law — while the British Standards define what competent maintenance looks like.

Where absolute certainty is needed for a client document, verify against the current BSI edition.